| Alternative NSN: 5925-00-780-8620 |
| Item Name: Circuit Breaker |
| CAGE Code : 74193 , 24446 , 77342 , 79405 |
| NIIN: 007808620 |
| FSC Name: 5925 Circuit Breakers |
| NCB Code: USA (00) |
| Manufacturers: eaton corporation , general electric company , tyco electronics corporation , wood electric operations potter and brumfield |
|
Part No Part No
|
Manufacturer |
Item Name Item Name
|
QTY QTY
|
RFQ RFQ
|
|---|---|---|---|---|
| AM12MG6-35-250-4-60 | eaton corporation | circuit breaker | Avl | |
| AM12MG6-35-250VAC60C4 | eaton corporation | circuit breaker | Avl | |
| 7759962P10REVA | general electric company | circuit breaker | Avl | |
| 122-235-101 | tyco electronics corporation | circuit breaker | Avl | |
| 122-235-101 | wood electric operations potter and brumfield | circuit breaker | Avl |
| MRC | Criteria | Characteristic |
|---|---|---|
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT AND EXPLOSION RESISTANT |
| CWJK | CASE MATERIAL | PLASTIC |
| AAQL | BODY STYLE | SINGLE POLE TYPE |
| ADAQ | BODY LENGTH | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
| ADAT | BODY WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM |
| AKPX | POLE QUANTITY | 1 |
| APNQ | ARC QUENCHING METHOD | AIR |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 35.0 AMPERES AC SINGLE LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 4.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
| FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| THSD | THREAD SERIES DESIGNATOR | UNC |
| TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
Before You Go, You Should Consider Looking at Our NSN Parts Catalog. and Remember, ASAP Sourcing Solutions Has Some of the Fastest and Most Competitive Quotes On the Market.
Request for Quote