| Alternative NSN: 5925-00-995-0857 |
| Item Name: Circuit Breaker |
| CAGE Code : 81348 , 95105 , 56365 |
| NIIN: 009950857 |
| FSC Name: 5925 Circuit Breakers |
| NCB Code: USA (00) |
| Manufacturers: federal specifications , rockwell collins aerospace , schneider electric gmbh |
|
Part No Part No
|
Manufacturer |
Item Name Item Name
|
QTY QTY
|
RFQ RFQ
|
|---|---|---|---|---|
| W-C-375-4 | federal specifications | circuit breaker | Avl | |
| WC375 04 004 | federal specifications | circuit breaker | Avl | |
| 214-0006-008 | rockwell collins aerospace | circuit breaker | Avl | |
| Q1-3100 | schneider electric gmbh | circuit breaker | Avl |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAQ | BODY LENGTH | 6.250 INCHES NOMINAL |
| ADAT | BODY WIDTH | 2.230 INCHES NOMINAL |
| ADAU | BODY HEIGHT | 2.650 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.738 INCHES MINIMUM AND 0.748 INCHES MAXIMUM |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | 0.220 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 TERMINAL |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 6.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CWJK | CASE MATERIAL | PLASTIC |
| FEAT | SPECIAL FEATURES | TO MAKE THIS CB COMPATIBLE TO THE SUBSTITUTE CB YOU MUST ADD EITHER P/N PK1MB,5925-01-429-4530 AND/OR P/N SK5669,5925-01-429-4529. |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| TEST | TEST DATA DOCUMENT | 81348-W-C-375 SPECIFICATION INCLUDES ENGINEERING TYPE BULLETINS,BROCHURES,ETC.,THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT EXCLUDES COMMERCIAL CATALOGS,INDUSTRY DIRECTORIES,AND SIMILAR TRADE PUBLICATIONS,REFLECTING G |
| TTQY | TERMINAL TYPE AND QUANTITY | 3 CLIP AND 3 COMPRESSION |
| ZZZK | SPECIFICATION/STANDARD DATA | 81348-W-C-375/4 GOVERNMENT SPECIFICATION |