Upload| Part Number : P120 | NSN : 5925009528641 |
|
| Manufacturer : Siemensallis Inc | CAGE Code : 60555 | FSC Details : 5925 Circuit Breakers |
| NIIN : 009528641 | INC Code : 00136 | Country : USA |
| NCB Code : 00 |
Thank You for Submitting Your RFQ for Part Number P120 by Siemensallis Inc
We always put our customers’ needs first, and we are always just a click or call away from assisting you throughout the purchasing process whenever you need it. Please do not hesitate to call our toll-free number +1-714-705-4780 for any inquiries about part number P120, or send us an email listing your needs, and we will get back to you as soon as possible. Whatever your requirements may be, we will not rest until we have fulfilled all your operational needs with highly competitive options.
| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-00-952-8641 Item PartTypeName: CIRCUIT BREAKER | 5925 | 009528641 | 0 | P | ||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| U | A | |||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| 41120 | 3 | 9 | 5 |
| MRC | Criteria | Characteristic |
|---|---|---|
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AKPX | POLE QUANTITY | 1 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED HOLE |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC SINGLE LOCATION |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC SINGLE LOCATION |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC SINGLE LOCATION |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY SINGLE LOCATION |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
| CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 0.800 NOMINAL SINGLE LOCATION |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH BUTTON |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CQJX | NOMINAL THREAD SIZE | 0.190 INCHES |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.020 NOMINAL AT 200 PCT SINGLE LOCATION |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
| CWJK | CASE MATERIAL | PLASTIC |
| FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
| THSD | THREAD SERIES DESIGNATOR | UNF |
| TTQY | TERMINAL TYPE AND QUANTITY | 2 SCREW |